Indicating Ringbalance
measuring draft, pressure and differential pressure of gaseous mediums.

Measuring Principle
Ringbalance system, factory-filled ringbody, supported by ball bearings
Measuring Ranges
from 0-50 Pa (0.2" W.C.) to 0-1.8 kPa (7" W.C.)
also plus/minus ranges, such as -25/0/+25 Pa
Scale units
Pa, daPa, kPa, mbar, mmWS, mmW.C.; in.W.C.
Accuracy
max. error +/-1.5% of span, below 100 Pa: +/-1.5 Pa
Pressure Connections
2 fittings for flexible tubes, 8mm outside diameter
Housing
for wall mounting or panel mounting, made out of glass reinforced black polycarbonate, protection class IP40 (optional IP55)
Weight: 2.8 kg
Temperature
operating temperature 0...50°C (32...122 °F)

Options:

Mechanical Contacts "MK"
rated at 250V / 30 VA; usable for ranges greater than 200 Pa,
Single contact: switching mode MIN or MAX,
Dual contact: MIN/MIN, MIN/MAX or MAX/MAX

Inductive Contacts (proximity sensors) "IK"
Type P&F, SJ3,5 to be connected to external contact amplifiers,
switching modes:
single: MIN or MAX, dual: MIN/MIN, MIN/MAX or MAX/MAX

Ordering specifications:
1. Type Indicating Ringbalance
2. Housing wall- or panel mounting
3. Range     
4. Power supply please specify
( 5. Overpressure )  please note if you expect that the measuring range could be exceeded,
(see: Overload-Protection )




Indicating Ringbalance


click to enlarge
Wall Mounting Panel Mounting
click to enlarge