Controller
electronic continuous-output controller with PID characteristics
Control Outputs
0-20mA, 4-20mA, 0-10V
Loads
mA-outputs: max. 680 ohm; Volt-output: min. 2k ohm
Control Settings
P (proportional band), D (differential action), I (integral action), HAND/AUTO, INVERT.
The response of the controller is tailored to the characteristics of the measuring system.
Setpoint adjustment
normal operation: by positioning the internal pointer "W"
external shifting by potentiometer (terminals 5-8)
LED
indicating output status (0% / 100%)
Power supply
230 VAC, (24/110/120/240 VAC); (3,5 VA)
Measuring System
Ringbalance principle, factory-filled ringbody, supported by ball-bearings
Measuring pickup
magnetic field sensor, non-contact and with infinite resolution
Ranges
from 0-50 Pa (0.2" W.C.) to 0-1.8 kPa (7" W.C.)
also plus/minus ranges, such as -25/0/+25 Pa
Scale units
Pa, daPa, kPa, mbar, mmWS, mmW.C.; in.W.C.
Accuracy
max. error +/- 1.5% of span, below 100 Pa: +/-1.5 Pa
Pressure connections
2 fittings for flexible tubes, 8mm outside diameter
Electrical connections
screw terminals, 3 cable fittings PG9 with strain relief
Housing
for wall mounting or panel mounting, made out of glass reinforced black polycarbonate, protection class IP40 (optional IP55)
Weight: 2.8 kg
Temperature
operating temperature 0...50°C (32...122 °F)
Electromagnetic Compatibility
according to EN 50081-2 (emission) and EN 50082-2 (immunity)
| Ordering specifications: | ||
| 1. | Type | RIXOTACT'S |
| 2. | Housing | wall- or panel mounting |
| 3. | Range | |
| 4. | Power supply | please specify |
| ( 5. | Overpressure ) | please note if you expect that the measuring range could be exceeded, (see: Overload-Protection ) |